Encoder data - incremental encoder
Figure 8-23
Entering the encoder data
⇒ Enter the encoder type (usually HTL/TTL), the number of pulses per revolution, the level
and the zero mark configuration
NOTICE
Terminal X177.41 always delivers +15 V to supply the incremental encoder. That is
independent of the "voltage supply" setting selected in the box.
Note
The SMC30 supplies 5 V / 24 V encoder supply.
⇒ Click Next >
Encoder data - Actual EMF value
⇒ Specify the EMF at maximum speed.
(The EMF must be specified as a percentage of the voltage shown in the screen).
⇒ Click Next >
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
8.4 Commissioning with the STARTER commissioning tool