Download Print this page

Siemens SINAMICS DCM Manual page 246

Dc converter
Hide thumbs Also See for SINAMICS DCM:

Advertisement

Terminal type
X524
Terminal type
Connectable conductor
cross-section
Stripped length
Tool
Tightening torque
X531 - X536
Terminal type
Connectable conductor
cross-section
Stripped length
7.5.3.2
X500 and X501 DRIVE-CLiQ interfaces
Table 7- 39
X500/X501: DRIVE-CLiQ interfaces
Pin
1
2
3
4
5
6
7
8
A
B
Connector type
RJ45 socket
The blanking covers for the DRIVE-CLiQ interfaces are included in the scope of delivery.
Blanking covers (50 pcs) article number: 6SL3066-4CA00-0AA0
Note
The maximum DRIVE-CLiQ cable length is 100 m.
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Screw terminal
Rigid, flexible
With wire-end ferrule without plastic sleeve
With wire-end ferrule with plastic sleeve
7 mm
0.6 × 3.5 mm screwdriver
0.5 to 0.6 Nm
Spring-loaded terminal
Rigid
Flexible
Flexible, with end sleeve without plastic sleeve
Flexible, with end sleeve with plastic sleeve
AWG / kcmil
10 mm
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
ac.maher.co.ir
Additional system components
7.5 Terminal Module TM150
0.08 mm
to 2.5 mm
2
0.5 mm
to 2.5 mm
2
0.5 mm
to 1.5 mm
2
0.2 mm
to 1.5 mm
2
0.2 mm
to 1.5 mm
2
0.25 mm
to 1.5 mm
2
0.25 mm
to 0.75 mm
2
24 to 16
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
Power supply, max. 450 mA
Electronics ground
2
2
2
2
2
2
2
247