Download Print this page

Siemens SINAMICS DCM Manual page 213

Dc converter
Hide thumbs Also See for SINAMICS DCM:

Advertisement

Additional system components
7.3 Terminal Module TM15
7.3
Terminal Module TM15
7.3.1
Description
The Terminal Module TM15 is a terminal expansion for snapping on to an EN 60715
mounting rail. The TM15 can be used to increase the number of available digital
inputs/outputs within a drive system.
Table 7- 16
Type
DRIVE-CLiQ interfaces
Digital inputs/outputs
7.3.2
Safety instructions
WARNING
Danger to life through non-observance of the safety instructions
If the safety instructions in Chapter 1 are not observed, accidents can occur involving
severe injuries or death.
• Make sure that the safety instructions are observed.
WARNING
Risk of fire through overheating if there are insufficient ventilation clearances
Inadequate ventilation clearances cause overheating with a risk for personnel due to smoke
and fire. This can also result in more downtimes and reduced service lives of the Terminal
Module.
• For this reason, it is imperative that you maintain the 50 mm clearances above and
below the Terminal Module.
NOTICE
Damage through the use of incorrect DRIVE-CLiQ cables
Damage or malfunctions can occur on the devices or system when incorrect or unreleased
DRIVE-CLiQ cables are used.
• Only use suitable DRIVE-CLiQ cables that have been released by Siemens for the
respective application.
214
Interface overview of the TM15
Number
2
24 (electrical isolation in 3 groups each with 8 DI/O)
ac.maher.co.ir
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001

Advertisement