7.3.10
Technical data
Table 7- 23
Technical data
6SL3055-0AA00-3FAx
Electronic power supply
Voltage
Current (without DRIVE-CLiQ or digital outputs)
Power loss
Ambient temperature up to an altitude of 2000 m
Storage temperature
Relative humidity
Peripherals
Digital inputs/outputs
Number of digital inputs/outputs
Electrical isolation
Max. cable length
Digital inputs
Voltage
Low level (an open digital input is interpreted as
"low")
High level
Input impedance
Power consumption (at 24 VDC)
Max. voltage in OFF state
Current in OFF state
Typical input delay of the digital inputs
Digital outputs (continuously short-circuit proof)
Voltage
Max. load current per digital output
Output delay (resistive load)
Typical
Maximum
Min. output pulse
(100% amplitude, 0.5 A with resistive load)
Switching frequency
For resistive load
For inductive load
For lamp load
Max. lamp load
Max. switching frequency
(100% amplitude, 50%/50% duty cycle;
with 0.5 A and a resistive load)
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Unit
V
DC
A
DC
W
° C
° C
5% to 95%, no condensation
Can be parameterized as either DI or DO
24
Yes, in groups of 8
m
V
DC
V
DC
V
DC
mA
V
DC
mA
μs
V
DC
A
DC
μs
μs
μs
Hz
Hz
Hz
W
kHz
ac.maher.co.ir
Additional system components
7.3 Terminal Module TM15
Value
24 (20.4 – 28.8)
0.15
< 3
0 - 60
-40 to +85
30
-30 to +30
-30 to +5
15 to 30
2.8
11
5
0.0 to 1.0 (per channel)
"0" → "1": 50
"1" → "0": 100
24
0.5
"0" → "1": 50
"1" → "0": 150
"0" → "1": 100
"1" → "0": 225
125 (typ.)
350 (max.)
max. 100
max. 0.5
max. 10
5
1 (typ.)
225