OFF3
E-STOP
Operating enable The current is reduced to zero at the slave, then the slave goes into
As long as the master does not receive a switch-on command, the slaves stay in oper-
ating state o10.0 (wait for switch-on from the master).
If the master receives a switch-on command, then it automatically transfers this to the
slaves. Then, all devices carry out their switch-on sequence, i.e. they attempt to go
into operating state o0. However, the master waits in operating state o1.7 until all
slaves have reached operating state o0 (exception: n+m operation for a 6-pulse paral-
lel connection)
If a slave leaves operating state o0, then the master outputs fault message F60044
(exception: n+m operation for a 6-pulse parallel connection)
• The speed setpoint and the actual speed value should be entered at the master
converter.
• The optimization runs should be started at the master converter. The slave converters
must be connected and ready for operation at this point.
Miscellaneous
Note
For a slave converter the i
because for a non-symmetrical current, this would then respond at the slave.
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
10.27 Connecting units in parallel and in series
no effect, as long as n<nmin has not been reached, then the cur-
rent is reduced to zero at the slave and the slave goes into operat-
ing state o9.1 or 9.2
The current is reduced to zero at the slave, then the slave goes into
operating state o10.3
operating state o1.1 or o1.
t monitoring of the motor should be deactivated (p50114=0),