3-ph. 830 VAC, 2Q devices
6RA8088-6LS22-0AA0
Table 4- 22
Technical data for 3-ph. 830 VAC, 2Q devices
Common data
Rated
armature supply voltage
1)
Rated
field supply voltage
1)
Electronic power supply,
rated supply voltage
Rated DC voltage
1)
Rated
field DC voltage
1)
Rated frequency
Overload possibility
6)
Closed-loop control constancy
Degree of protection
Protection class
Table 4- 23
Technical data for 3-ph. 830 VAC, 900 A to 1900 A, 2Q devices
Article number 6RA80 ..
Rated DC current
Rated armature input current
Rated power
Power loss at
rated DC current (approx.)
Rated field DC current
Type of cooling
Rated
fan
supply voltage
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
6RA8093-4LS22-0AA0
V
3-ph. 830 VAC (+10% / -20%)
V
2-ph. 480 VAC (+10% / -20%)
V
2-ph. 380 (-25%) to 480 VAC (+10%); In = 1 A or
1-ph. 190 (-25%) to 240 VAC (+10%); In = 2 A
(-35% for 1min.)
With option L05: 18 to 30 VDC; In = 5 A
V
1000
V
390
Hz
45 to 65
10)
Max. 1.8x rated DC current
Δn = 0.006% of the rated motor speed during operation with
incremental encoder and digital setpoint
Δn = 0.1% of the rated motor speed during operation with
analog tachometer or analog setpoint
IP00 acc. to DIN EN 60529
Class I (with protective conductor system) and class III (PELV)
according to EN 61800-5-1
..88-6LS22-...
A
A
2)
kW
W
4221
A
Forced ventilation
50 Hz
V
3-ph. 400 VAC (±10%)
60 Hz
/ clockwise phase se-
quence
3-ph. 460 VAC (±10%)
/ clockwise phase se-
quence
ac.maher.co.ir
6RA8095-4LS22-0AA0
5)
..93-4LS22-...
950
1500
789
1245
950
1500
7122
40
40
Forced ventilation
3-ph. 400 VAC (±10%) / clockwise phase se-
3-ph. 460 VAC (±10%) / clockwise phase se-
Technical data
4.3 Unit data
..95-4LS22-...
1900
1577
1900
8669
40
Forced ventilation
quence
quence