6.10
Installation notes for installation according to UL 508C
● "Solid state motor overload protection at 110 % of full-load current is provided in each
model", or equivalent.
● "Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes", or the equivalent.
● Blower motor protection type 3RV1011-0EA1 trimmed to 0.33 A manufactured by
Siemens is to be provided for blower motor type R2D225-RA26-11 in drive model sizes C
and D.
● Blower motor protection type 3RV1011-0GA1 trimmed to 0.50 A manufactured by
Siemens is to be provided for blower motor Type R2D250-RA28-17 in drive model size E.
● Blower motor protection type 3FV1011-0KA1 trimmed to 1.25 A manufactured by
Siemens is to be provided for blower motor Type RH28M-2DK.3F.1R in Drive model size
F.
Table 6- 44
Overview of Frame Sizes (in mm)
Size
Width
A
385
B
385
C
625
D
700
E
780
F
880
SINAMICS DCM DC Converter
Operating Instructions, 02.2015, A5E34763375/RS-AA/001
Height
Depth
268
210
268
250
268
275
268
310
268
435
448
505
ac.maher.co.ir
6.10 Installation notes for installation according to UL 508C
Line voltage (V)
400, 480
400, 480, 575
400, 480, 575
400, 480, 575
400, 480, 575
400, 480, 575
Connecting
Output current (A)
15 - 30
60 - 280
400 - 600
760 - 850
1000 - 1200
1600 - 3000