15.5.5.4 Connection to the PLC

The following section describes how to connect a Vision Sensor to a PLC. Connection to an Allen Bradley
Compact Logix L16ER with Studio 5000 software serves as an example.
15.5.5.4.1

Determining a permanent IP address and name for the Vision Sensor

The Vision Sensor is not visible in the EtherNet/IP device list once it is connected to the PLC, since data
transmission via EtherNet/IP is disabled in the Vision Sensor's factory settings.
This section describes how a persistent IP address is assigned and a device name determined for the Vision
Sensor.
1.
After connecting the Vision Sensor to the PLC,
the RSLinx contained in the Rockwell software
package can be used to monitor whether the
connected Vision Sensor is visible.
It is not, since the factory settings mean that
EtherNet/IP is disabled in the Vision Sensor.
2.
Open the Application Suite.
3.
Connect to the desired Vision Sensor.
4.
Switch to Configuration operating mode.
Open the Device settings  process interface.
5.
v2.11.0-B4
369/429