15.4.3 Command GA – temperature alarm queries
This function enables you to query the device's current temperature status.
An internal protection device intervenes when the device is operated outside of specification; this is intended
to protect the components against destruction by heat.
The Application Suite, the web-interface and the process interfaces will output an overheating warning to
notify users that the maximum permissible operating temperature has been reached (circa 85–90% of
loading, see the Request GT heat state command).
Should the housing temperature continue to rise, the device will undergo emergency shutdown to protect it
from damage.
Example
Structure of the command PLC
Command
Parameters
G
A
Get Alarm
none
Structure of the Response PLC
Response
R
A
0
0
Response
8 byte ASCII hex
Alarm
Temperature status
Parameters of the "RA" command – current temperature status
The current temperature status will be transmitted using 8 characters, where the first 7 characters in a bit
mask are always 0 and the current temperature status is contained in bits 0 and 1 of the eighth character.
Bits
3
2
1. ASCII characters
3. ASCII characters
5. ASCII characters
7. ASCII characters
v2.11.0-B4
device
device
0
0
0
0
0
0
1
0
0
0
0
0
3
2
2. ASCII characters
4. ASCII characters
6. ASCII characters
8. ASCII characters
0
308/429
Technical Documentation
VeriSens
1
0
0
0
0
Thermal
Heat
shutdown
warning
Baumer Optronic GmbH
Radeberg, Germany
®

Advertisement

Table of Contents
loading

Table of Contents