Interconnect Port Networks with Fiber Optic Cabling
3. Behind control carrier A of EPN cabinet 2:
4. Behind control carrier A of EPN cabinet 3:
555-233-115
Carefully attach the fiber optic cable (with cable ties) to the wall of
the cable tray at the built-in cable tie positions.
Coil up the surplus fiber cable and place it in the cable manager.
Install a lightwave transceiver on the cable connector at slot 2A02.
Connect a fiber optic cable to the transceiver just installed.
Route the cable to the cable tray and down, out of the cabinet,
through the cable manager to the PDS cross-connect facility.
Connect the fiber cable to the lightguide interconnect unit provided.
Carefully attach the fiber optic cable (with cable ties) to the wall of
the cable tray at the built-in cable tie positions.
Install a lightwave transceiver on the cable connector at slot 3A02.
NOTE:
Attenuators may be required for single mode fiber using a
300A Lightwave Transceiver
Connect the remaining end of the cable to the transceiver just
installed.
Route the cable to the cable tray and down, out of the cabinet,
through the cable manager to the PDS cross-connect facility.
Connect the fiber cable to the lightguide interconnect unit provided.
Carefully attach the fiber optic cable (with cable ties) to the wall of
the cable tray at the built-in cable tie positions.
Coil up the surplus fiber cable and place it in the cable manager.