WAGO-I/O-SYSTEM 750
750-8208 PFC200 CS 2ETH RS CAN DPM
11
PROFIBUS DP-V1 Master
Observe CODESYS Version
A CODESYS Version higher than or equal to 2.3.9.49 is required for operation of
the controllers "PFC200 CS 2ETH RS CAN DPM" (750-8208)!
11.1
PLC configuration
11.1.1
Configuration of PROFIBUS master and slaves
Before an application has access to the connected PROFIBUS network, it must be
configured in CODESYS:
1.
To add the PROFIBUS Master to the PLC configuration, right-click "PBM
unused[Slot]" and select "Replace element > PROFIBUS DP-V1 Master".
Figure 144: Appending the PROFIBUS master
2.
To select one (or more) PROFIBUS slaves, right click on the PROFIBUS
Master ("PROFIBUS DP-V1 master[SLOT]")) and select "Append
Subelement".
In the following example the 750-343 PROFIBUS coupler (FW:08) was
selected as slave. Note that the firmware version of the slave must match the
selected GSD file.
Manual
Version 1.1.0, valid from FW Version 02.06.20(09)
PROFIBUS DP-V1 Master
339