Normally, you must only check the baud rate on the CAN parameters tab.

Figure 113: CAN Parameters Tab (Master)

Table 214: Description of the CAN Parameters (Master)

Parameters
Baud rate
Com. Cycle Period (µsec)
Sync. Window Length
(µsec)
Sync. COB-ID
Node ID
Start automatically
Manual
Version 1.1.0, valid from FW Version 02.06.20(09)
Explanation
Specify the baud rate that will apply to the transfer
on the CAN bus (default setting: 125000 baud).
Specify the time interval (in µsec) that the
synchronization notification will be sent by the
controller. Smallest time interval: 1000 µsec
Not currently implemented.
You can enable or disable sending of
synchronization notification by the controller.
Default setting: COB ID 128 (0x80).
Station address (node ID) of the controller on the
CAN bus.
When you mark this check box, the controller
automatically sets the CAN master and slaves to the
"Operational" based on the defined parameters.
If you do not mark this check box, starting can be
performed using the CIA405NMT library command.
CANopen Master and Slave
307