Advertisement

80

Appendix

10
Appendix
10.1
Configuration and Parameterization using a GSD
File with PROFIBUS DP and PROFINET IO
Behavior after Overwriting with WAGO-I/O-CHECK !
If WAGO-I/O-CHECK is used to overwrite a parameterization made with the
GSD file, the I/O module operates with the WAGO-I/O-CHECK settings until the
750-333 and 750-833 Fieldbus Couplers/Controllers are restarted.
After restart, the I/O module is re-parameterized via PROFIBUS using the GSD
settings.
10.1.1

4AI U/I Diff/Galv Configuration

10.1.1.1

PROFIBUS DP Fieldbus Couplers/Controllers 750-333(/0xx-000),

750-833(/0xx-000)

When using the aforementioned PROFIBUS DP fieldbus devices, the process
image size is configured by selecting the corresponding GSD entry.

Table 45: PROFIBUS DP Configuration

GSD Entry
Module
75x-471 4AI/U/I Diff/Galv
75x-471 4AI/U/I Diff/Galv RA
PFC 75x-471 4AI/U/I Diff/Galv
10.1.1.2

PROFINET IO Fieldbus Couplers 750-375(/025-000), 750-377(/025-000)

When using the aforementioned PROFINET IO fieldbus couplers, the process
image size is configured by selecting the corresponding GSD entry.

Table 46: Configuration 750-375(/025-000) und 750-377(/025-000)

GSD Entry
Module
75x-471 4AI, U/I
Manual
Version 1.0.0
PI-Length/[Byte]
Sub-
Module
n/a
Sub-Module
4AI, INT16[4] I
4AI, {UINT8, INT16}[4]
I/O
WAGO-I/O-SYSTEM 750
750-471 4AI U/I Diff Galv
Data Type
I
O
8
n/a
INT16
12
12
{UINT8, INT16}
n/a
n/a
PI-Länge/[Byte]
Data Type
I
O
8
n/a
INT16
12
12
{UINT8, INT16}
Inst.
4
n/a
n/a
Inst.
4