90
Commissioning
</dg_
7.5

Initiating Reset Functions

You can initiate various reset functions using the mode selector switch and the
Reset button (RST).
7.5.1

Warm Start Reset

The CODESYS 2 application is reset on a warm start reset. This corresponds to
</dg_
the WAGO I/O PRO IDE "Reset" command.
To perform a warm start reset, set the mode selector switch to "Reset" and hold it
</dg_
there for two to seven seconds.
Execution of the reset is signaled by the red "RUN LED" briefly going out when
the mode selector switch is released.
7.5.2

Cold Start Reset

</dg_
On a cold start reset the CODESYS 2 application is reset and the memory
containing the retain variables is cleared.
This corresponds to the WAGO I/O PRO IDE "Reset (Cold)" command.
</dg_
To perform a cold start reset, set the mode selector switch to "Reset" and hold it
there for more than seven seconds.
Execution of the reset is signaled after seven seconds by the "RUN" LED going
out for an extended period. You can then release the mode selector switch.
</dg_
7.5.3

Software Reset

The controller is restarted on a software reset.
To perform a software reset, set the mode selector switch to RUN or STOP and
then press the Reset button (RST) for one to eight seconds.
All LEDs will light up briefly in green to signal reset completion.