Device Description
3.3.7
CANopen – X4 Fieldbus Connection
Figure 12: CANopen – X4 Fieldbus Connection
Table 11: Legend for Figure "CANopen – X4 Fieldbus Connection"
Contact
1
2
3
4
5
6
7
8
9
DC/DC converters and optocouplers in the fieldbus interface provide electrical
isolation between the CANopen bus system and the electronics.
The cable shield must be applied to the CAN shield. This is terminated to ground
in devices with 1 MΩ (DIN rail contact). A low-impedance connection of the
shielding to ground is possible only from the outside (e.g., by a supply module).
We recommend using central ground contacts for the entire CANopen bus line
shielding.
To minimize reflection at the end of the line, the CANopen line must be
terminated at both ends by a cable termination.
Attention - bus termination!
The CANopen bus segment must be terminated at both ends!
No more than 2 terminations per bus segment may be used!
Terminations may not be used in stub and branch lines!
Operation without proper termination of the CANopen network may result in
transmission errors.
Signal
-
CAN_L
GND
-
Drain Shield
-
CAN_H
-
CAN_V+
Version 1.1.0, valid from FW Version 02.06.20(09)
WAGO-I/O-SYSTEM 750
750-8208 PFC200 CS 2ETH RS CAN DPM
Description
Not used
CAN Signal Low
Ground
Not used
Shield termination
Not used
CAN Signal High
Not used
Not used
Manual