With Hart Dynamic Variables On Profibus Dp/V1 750-333 And 750-833 - WAGO 753-482 Manual

2ai 4-20ma 12 bit s.e. hart 2-channel analog input; 4-20 ma; hart; single-ended (s.e.) for wago i/o system 750
Table of Contents

Advertisement

WAGO I/O System 750
753-482 2AI 4-20mA 12 Bit S.E. HART
14.
Now move the mouse to "<ModbusCommChannel:-> 075x-08xx DTM*" in
the tree structure and click on [Add...] in the context menu (right mouse
button).
Select the HART DTM for your HART field device in the dialog which opens
and confirm the selection by clicking [OK].
A further view will appear in the dialog window in which you can now select
the channel to which your HART device is connected. Select "M01_Ch01"
for Channel 1 of the first plugged-in HART module or "M01_Ch02" for
Channel 2.
Confirm the selection by clicking [OK].
Depending on the entry "<M01_Ch01:0>...HART DTM*" or
"<M01_Ch02:0>...HART DTM*" will be added in the tree structure.
If a HART device is connected to both channels, carry out these steps for
the first channel and then again in a similar manner for the second channel.
15.
Move the mouse once again to "<ModbusCommChannel:-> 075x-08xx
DTM*" in the tree structure and select it by clicking with the left mouse
button.
Next go to "Set up connection" on the Device menu. The entry
"<ModbusCommChannel:-> 075x-08xx DTM*" will now be changed to
italics in the tree structure.
16.
Next go to "More functions" on the Device menu and click on Device list
on the sub-menu.
A dialog window with a list of devices will open.
Click on [Update].
After a while the DTM(s) for the connected HART devices will now also be
shown in green.
17.
Move the mouse once again to the entry for the channel to which your
HART device is connected in the tree structure and select it by clicking with
the left mouse button.
Go to the Device menu and click Set up connection. This entry will then
be changed to italics in the tree structure.
If a HART device is connected to both channels, carry out these steps for
the first channel and then again in a similar manner for the second channel.
18.
Move the mouse to the entry for the channel to which your HART device is
connected in the tree structure and double-click it; a dialog window with the
online parameterization will then open. After a short time connection
symbols will be displayed after the respective parameters.
9.3
With HART Dynamic Variables on PROFIBUS DP/V1
750-333 and 750-833
When connecting to the PROFIBUS DP/V1 Coupler 750-333 or Controller
750-833, there is a choice of four operating modes, "2AI + 1, 2, 3, 4 HART
variables per channel", in which the incorporation of one, two, three or four HART
variables per channel in the cyclic process image can be set up for the analog
values.
Commissioning
71