WAGO-I/O-SYSTEM 750
750-8208 PFC200 CS 2ETH RS CAN DPM
11.3.7
Analyzing PROFIBUS Diagnostics of Individual I/O Modules
The array elements [0] to [22] listed in the illustration below are reserved for the
PROFIBUS standard diagnostics. From array element [23] onwards, they include
diagnostic information from the WAGO I/O modules.
The amount of diagnostic information per channel of an I/O module (not
PROFIsafe) is 3 bytes.
Figure 172: Online view of the EXTENDEDINFO array in binary representation
The diagnostic information on the EXTENDEDINFO array is described in the
following section.
Manual
Version 1.1.0, valid from FW Version 02.06.20(09)
PROFIBUS DP-V1 Master
369