Figure 13: Canopen Standard Bus Termination; 750-8208 Pfc200 Cs 2Eth Rs Can Dpm - WAGO I/O SYSTEM 750 Manual

750-8208 pfc200 cs 2eth rs can dpm plc - controller pfc200
Hide thumbs Also See for I/O SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750

750-8208 PFC200 CS 2ETH RS CAN DPM

Observe permissible resistor power loss!
For normal operation, 1/4 Watt resistors are sufficient. In the event of a short
circuit (24 V power supply to a bus line), the resistor is subjected to a power loss
of (short-circuit output current from transceiver * power supply voltage). The
resistor must be designed to withstand this power loss level.

Figure 13: CANopen Standard Bus Termination

Manual
Version 1.1.0, valid from FW Version 02.06.20(09)
Device Description