Table 325: Description of Configuration Scripts for "Ports and Services" – "PLC Runtime Services"
Parameters Status Call
General Settings
PLC runtime
version
Boot project
location
Default web
page
Change
authentication
password
Manual
Version 1.1.0, valid from FW Version 02.06.20(09)
get_runtime_config
read
running-version
config_runtime runtime-
write
version=<value>
get_runtime_config
read
boot-project
config_runtime boot-
write
project=<value>
get_runtime_config
read
default-webpage
config_runtime default-
write
webpage=<value>
config_linux_user
user=admin new-
write
password=<value>
confirm-
password=<value>
Output/Input
Version of the enabled PLC
runtime
Possible return values:
-
0 = no runtime enabled
-
2 = CODESYS 2 enabled
3 = e!RUNTIME enabled
-
Setting and, if necessary,
stopping of the previous runtime
version and starting of required
version
Possible entries for <value>:
-
0 = do not enable runtime
-
2 = enable CODESYS2
3 = enable e!RUNTIME
-
Memory location for a boot
project of the runtime application
Possible return values:
-
HOME:// (saving on internal
memory)
-
CARD:// (saving on the
memory card)
Possible entries for <value>:
-
HOME:// (saving on internal
memory)
-
CARD:// (saving on the
memory card)
Calling web page when only
entering the IP address in the
web browser
Possible return values:
-
WBM (web based
management)
-
Webvisu (web visualization)
Possible entries for <value>:
-
WBM (web based
management)
-
Webvisu (web visualization)
Change the PLC runtime access
password
Appendix
441
Effecti
ve
Immedi
ately
Immedi
ately
Immedi
ately
Immedi
ately

Advertisement