Commissioning
7.6.4

Configuration using a Terminal Program (CBM)

You can use the Console-Based Management Tool (CBM) to configure the
controller via the ETHERNET interface and SSH, as well as the RS-232 interface
and Linux
To establish a connection via the serial interface, set the baud rate to 115200 baud
in the terminal program. The settings for data bits, stop bits and parity do not need
to be adjusted.
To launch the CBM, log in to the Linux
(case sensitive).

Figure 44: CBM main menu (example)

7.6.4.1

CBM Menu Structure Overview

Table 106: CBM Menu Structure

Menu Hierarchy
0. Quit
1. Information
0. Back to Main Menu
1. Controller Details
2. Network Details
2. PLC Runtime
0. Back to Main Menu
1. Information
2. General Configuration
3. WebVisu
3. Networking
0. Back to Main Menu
®
console.
750-8208 PFC200 CS 2ETH RS CAN DPM
®
console and enter the command "cbm"
Version 1.1.0, valid from FW Version 02.06.20(09)
WAGO-I/O-SYSTEM 750
Manual