As CANopen does not transfer data by bits, the variable data is combined from a
Boolean data type to bytes and assigned to the corresponding index; Boolean
input variable data is assigned to index 0xA080, Boolean output variable data to
index 0xA500.
Variable data that has a data width of 1 byte or more is assigned to the
corresponding indices in a similar manner.
Observe the direction of data flow!
The IEC 61131-3 input variables are defined from the perspective of the CAN
bus. These are output variables from the perspective of the PFC. Accordingly, the
IEC 61131-3 output variables are input variables for the PFC.
This table provides an overview of the indices of "IEC 61131-3" variables.

Table 208: Indexing of "IEC 61131-3" Variable Data in the Object Directory

Data Type
Integer8
Unsigned8
Boolean
Integer16
Unsigned16
Integer24
Unsigned24
Integer32
Unsigned32
Float32
Unsigned40
Integer40
Unsigned48
Integer48
Unsigned56
Integer56
Integer64
Unsigned64
Using the associated indices for data types with a data width of 1 byte (Integer8,
Unsigned8 and Boolean), read-only byte-by-byte access is possible from the
fieldbus to data in the controller memory.
The sub-index is utilized to select a specific byte.
Manual
Version 1.1.0, valid from FW Version 02.06.20(09)
IEC 61131-3 Output
Variables
0xA000
0xA040
0xA080
0xA0C0
0xA100
0xA140
0xA180
0xA1C0
0xA200
0xA240
0xA280
0xA2C0
0xA300
0xA340
0xA380
0xA3C0
0xA400
0xA440
CANopen Master and Slave
IEC 61131-3 Input
Variables
Index
0xA480
0xA4C0
0xA500
0xA540
0xA580
0xA5C0
0xA600
0xA640
0xA680
0xA6C0
0xA700
0xA740
0xA780
0xA7C0
0xA800
0xA840
0xA880
0xA8C0