3.8.8

CANopen

Table 25: Technical Data – CANopen
CANopen input and output process
image max.
No direct access from fieldbus to the process image for I/O modules!
Any data that is required from the I/O module process image must be explicitly
mapped in the CODESYS program to the data in the fieldbus process image and
vice versa! Direct access is not possible!
3.8.9

PROFIBUS

Table 26: Technical Data – PROFIBUS
PROFIBUS input and output process
image max.
No direct access from fieldbus to the process image for I/O modules!
Any data that is required from the I/O module process image must be explicitly
mapped in the CODESYS program to the data in the fieldbus process image and
vice versa! Direct access is not possible!
3.8.10

Serial interface

Table 27: Technical Data – Serial Interface
Interface
Protocols
750-8208 PFC200 CS 2ETH RS CAN DPM
2000 words
5000 bytes/5000 bytes
(a maximum 125 slaves are supported,
a slave's process image can have up to
244 bytes/244 bytes.)
1 x serial interface per TIA/EIA 232 and
TIA/EIA 485 (switchable), 9-pole D-sub
female connector
MODBUS RTU
Version 1.1.0, valid from FW Version 02.06.20(09)