WAGO I/O SYSTEM 750 Manual page 442

750-8208 pfc200 cs 2eth rs can dpm plc - controller pfc200
Hide thumbs Also See for I/O SYSTEM 750:
Table of Contents

Advertisement

442
Appendix
Table 325: Description of Configuration Scripts for "Ports and Services" – "PLC Runtime Services"
Parameters Status Call
CODESYS 2 Settings
CODESYS2
Webserver
State
CODESYS2
Port
Authentication
CODESYS2
Service State
CODESYS2
Communicatio
n Port
get_runtime_config cfg-
read
version=2 Webserver-
state
config_runtime cfg-
write
version=2 Webserver-
state=<value>
get_runtime_config cfg-
read
version=2 authentication
config_runtime cfg-
write
version=2
authentication=<value>
get_runtime_config
read
service-state
config_runtime service-
write
state=<value>
get_runtime_config
read
comm-port
config_runtime comm-
write
port=<value>
750-8208 PFC200 CS 2ETH RS CAN DPM
Output/Input
Read status of the runtime-
specific Webserver
Possible return values:
-
enabled
-
disabled
Enable/disable runtime-specific
Webserver
Possible entries for <value>:
-
enabled
-
disabled
Read status of the port
authentication for
communication between the
CODESYS 2 PC software and
the controller
Possible return values:
-
enabled
-
disabled
Possible entries for <value>:
-
enabled
-
disabled
Read status of the port for
communication between the
CODESYS 2 PC software and
the controller
Possible return values:
-
enabled
-
disabled
Possible entries for <value>:
-
enabled
-
disabled
Read value of set network port
for communication between PC
and controller
Default value is 2455
Change port number
Enter the TCP/IP port number for
<value>.
Version 1.1.0, valid from FW Version 02.06.20(09)
WAGO-I/O-SYSTEM 750
Effecti
ve
Immedi
ately
Immedi
ately
Immedi
ately
Immedi
ately
Manual

Advertisement

Table of Contents
loading

Table of Contents

Save PDF