Table 320: Description Of The Configuration Scripts For "Ntp - WAGO I/O SYSTEM 750 Manual

750-8208 pfc200 cs 2eth rs can dpm plc - controller pfc200
Hide thumbs Also See for I/O SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-8208 PFC200 CS 2ETH RS CAN DPM

Table 320: Description of the Configuration Scripts for "NTP"

Parameters Status Call
Configuration Data
State
Port
Time Server
Update Time
(seconds)
Manual
Version 1.1.0, valid from FW Version 02.06.20(09)
get_ntp_config
read
state
config_sntp
write
state=<Value>
get_ntp_config
read
port
config_sntp
write
port=<Value>
get_ntp_config
read
time-server-<N>
config_sntp
write
time-server-
<N>=<Value>
get_ntp_config
read
update-time
config_sntp
write
update-time=<Value>
Output/Input
Query the status of the NTP
server
Possible return values are:
-
enabled
-
disabled
Possible entries for <Value>:
-
enabled
-
disabled
Port number of the NTP server
Enter the port number for
<Value>.
Query the IP address of the time
server: N = 1 ... 4 for querying
one of 4 time servers.
Enter the IP address of 4 time
servers
<N> can be a value from 1 to 4.
<Value> is an IP address with
the format "Number. Number.
Number. Number."
Query the time in seconds
between two requests to the time
server.
Specify the time-server's query
cycle (in s) for <Value>.