750-8208 Pfc200 Cs 2Eth Rs Can Dpm - WAGO I/O SYSTEM 750 Manual

750-8208 pfc200 cs 2eth rs can dpm plc - controller pfc200
Hide thumbs Also See for I/O SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750

750-8208 PFC200 CS 2ETH RS CAN DPM

CANopen Master/Slave
PROFIBUS Master
In the controller, all input signals from the sensors are combined. After connecting
the controller, all of the I/O modules on the bus node are detected and a local
process image is created from these. Analog and specialty module data is sent via
words and/or bytes; digital data is sent bit by bit.
No direct access from fieldbus to the process image for I/O modules!
Any data that is required from the I/O module process image must be explicitly
mapped in the CODESYS program to the data in the fieldbus process image and
vice versa! Direct access is not possible!
Fieldbus configuration can be performed using the CODESYS 2.3 controller
configuration.
A Web-based management system (WBM) is also available as a configuration aid.
This system includes various dynamic HTML pages from which, among other
things, information about configuration and the status of the controller can be
called up. The WBM is already stored in the device and is presented and operated
using an Internet browser. You can also save your own HTML pages in the
implemented file system, or call up programs directly.
In the controller's initial state, the installed firmware is based on Linux
special real-time extensions of the RT-Preempt patch. In addition, the following
application programs are also installed on the controller, along with a number of
different auxiliary programs:
a SNMP server/client
a Telnet server
a FTP server, a FTPS server (explicit connections only)
a SSH server/client
a Web server
a NTP client
a BootP and DHCP client
a CODESYS Runtime Environment
Based on IEC-61131-3 programming, data processing takes place on site in the
controller. The logical process results can be output directly to the actuators or
transmitted via a connected fieldbus to the higher level controller.
Manual
Version 1.1.0, valid from FW Version 02.06.20(09)
Device Description
®
, with
25

Advertisement

Table of Contents
loading

Table of Contents