Description Of Diagnostic Information For Wago I/O Modules; Figure 173: Online View Of The Extendedinfo Array In Binary Representation; Table 240: Channel 1 Of The 750-466 Input Module - WAGO I/O SYSTEM 750 Manual

750-8208 pfc200 cs 2eth rs can dpm plc - controller pfc200
Hide thumbs Also See for I/O SYSTEM 750:
Table of Contents

Advertisement

372
PROFIBUS DP-V1 Master
11.3.7.2

Description of Diagnostic Information for WAGO I/O Modules

The WAGO I/O module diagnostic information is stored beginning with array
element EXTENDEDINFO[23]. Decoding of the diagnostic information is shown
here using the dual channel, 750-466 input module as an example.

Figure 173: Online view of the EXTENDEDINFO array in binary representation (1)

Table 240: Channel 1 of the 750-466 Input Module

Array Element Contents Explanation
30
31
32
10000100 Slot for input module; in this case the third (slot 4).
Note:
The first slot is reserved for the fieldbus coupler and
controller including the supply module. Therefore,
the first I/O module is inserted in the second slot.
01000000 The first two bits indicate the type of channel:
01
10
11
The other bits indicate the channel number.
10101000 The first three bits indicate the type of channel:
000
001
010
100
101
110
The other bits indicate I/O module errors.
Version 1.1.0, valid from FW Version 02.06.20(09)
WAGO-I/O-SYSTEM 750
750-8208 PFC200 CS 2ETH RS CAN DPM
Input channel
Output channel
Input and output channel
No assignment
1 bit
2 bits
1 byte
1 word
2 words