WAGO-I/O-SYSTEM 750
750-8208 PFC200 CS 2ETH RS CAN DPM
15.1.5.4

Serial Interface Modules with Standard Data Format

750-650/000-001, -014, -015, -016
750-653/000-001, -006
The above Serial Interface Modules with Standard Data Format have a total of 6
bytes of user data in both the Input and Output Process Image (5 bytes of serial
data and 1 byte of control/status). The following table illustrates the Input and
Output Process Image, which have a total of 3 words mapped into each image.
Word alignment is applied.

Table 290: Serial Interface Modules with Standard Data Format

Input and Output Process Image
Offset
0
1
2
15.1.5.5

Data Exchange Module

750-654, (and the variation /000-001)
The Data Exchange modules have a total of 4 bytes of user data in both the Input
and Output Process Image. The following tables illustrate the Input and Output
Process Image, which has a total of 2 words mapped into each image.
Word alignment is applied.

Table 291: Data Exchange Module

Input and Output Process Image
Offset
0
1
15.1.5.6

SSI Transmitter Interface Modules

750-630 (and all variations)
The process image of the / 003-000-variants depends on the parameterized
operating mode!
The operating mode of the configurable /003-000 I/O module versions can be set.
Based on the operating mode, the process image of these I/O modules is then the
same as that of the respective version.
Manual
Version 1.1.0, valid from FW Version 02.06.20(09)
Byte Destination
High Byte
D0
D2
D4
Byte Destination
High Byte
D1
D3
Low Byte
C/S
Data byte
D1
D3
Low Byte
D0
D2
Appendix
413
Description
Control/status
byte
Data bytes
Description
Data bytes