Data Memory and Function Block Limitation

The data memory is set for 64 Mbytes in the controller's initial state.
This set value has already been requested in the system after a successful program
download and can be fully utilized.
Together with the data memory to be used by the application, memory is required
for the individual program function blocks in the system.
The size of the administration space is calculated from the function block
limitation * 12 (i.e., normally 4096 * 12).
The actual size of the main memory required in the system for data is the sum of
global data memory and function block limitation memory.
This value should not exceed the value specified for "Size of entire data memory."

Figure 98: Data Memory and Function Block Limitation (Example)

750-8208 PFC200 CS 2ETH RS CAN DPM
Version 1.1.0, valid from FW Version 02.06.20(09)
WAGO-I/O-SYSTEM 750
Manual