Figure 108: State Diagram, Alternative_Watchdog Operation Mode - WAGO I/O SYSTEM 750 Manual

750-8208 pfc200 cs 2eth rs can dpm plc - controller pfc200
Hide thumbs Also See for I/O SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-8208 PFC200 CS 2ETH RS CAN DPM

Figure 108: State Diagram, ALTERNATIVE_WATCHDOG Operation Mode

The state diagram for the ALTERNATIVE_WATCHDOG operation mode shows
that the watchdog is always active as soon as a timeout time > 0 is set in the
register 0x1102 (Watchdog Timeout). The writing of commands in the register
0x1100 (Watchdog Command) is limited in this operation mode. Only the
WATCHDOG_START command is permitted as a possible trigger. The only
possibilities to deactivate or stop the watchdog in
ALTERNATIVE_WATCHDOG mode are the setting of the timeout register to 0
after the timeout has elapsed and the switching back to the
STANDARD_WATCHDOG operation mode.
The following diagram shows the possible state transitions when operation modes
are switched.