370
PROFIBUS DP-V1 Master
11.3.7.1
Description of Diagnostic Information on the Function Block
DiagGetState.EXTENDEDINFO for PROFIBUS
This section describes the EXTENDEDINFO[0-22] array for PROFIBUS
standard diagnostics.

Table 234: Diagnostic "EXTENDEDINFO"

Array Element
EXTENDEDINFO[0]
EXTENDEDINFO[1]
EXTENDEDINFO[2]
EXTENDEDINFO[3]
EXTENDEDINFO[4]
EXTENDEDINFO[5]
EXTENDEDINFO[6]
EXTENDEDINFO[7]
EXTENDEDINFO[8]
EXTENDEDINFO[9]
EXTENDEDINFO[10]
EXTENDEDINFO[11]
EXTENDEDINFO[12 ... 13]
EXTENDEDINFO[14 ... (8+X-1)]
Limited diagnostic information
Only the first 100 bytes of the array can be read out of this module.
The first 8 bytes in the EXTENDEDINFO are the header. This means that only 92
bytes of diagnostic information can be read out of the DP slave.

Table 235: Station status 1

Bit position Explanation
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Slave does not respond.
Slave is not ready.
Slave is incorrectly parameterized.
Used for extended diagnostics.
Slave detected unknown command.
Slave response not plausible.
Last parameter telegram erroneous.
Slave parameterized by a different master.
750-8208 PFC200 CS 2ETH RS CAN DPM
Explanation
Slave address
0 (free)
0 (free)
0 (free)
0 (free)
X, Diagnostic data length
10 (free)
1 (free)
Station status 1
Station status 2
Station status 3
Master address
The slave station communicates the 2 bytes
for its ident number.
Ext_Diag_Data (x > 6, for x <= 6 no
extended information available from slave)
Version 1.1.0, valid from FW Version 02.06.20(09)
WAGO-I/O-SYSTEM 750
Manual