Modbus - Codesys 2; General; Features - WAGO I/O SYSTEM 750 Manual

750-8208 pfc200 cs 2eth rs can dpm plc - controller pfc200
Hide thumbs Also See for I/O SYSTEM 750:
Table of Contents

Advertisement

262
MODBUS – CODESYS 2
9
MODBUS – CODESYS 2
</dg_
9.1

General

MODBUS is a non-vendor-specific, open fieldbus standard for a wide range of
applications in production and process automation. The MODBUS
communications protocol is based on a master/slave or client/server architecture
that uses function codes for execution of individual MODBUS services, which
have reading or writing access to individual or multiple elements of the MODBUS
data model simultaneously.
9.2

Features

The MODBUS slave implemented in the PFC200 has the following features:
3 modes: MODBUS TCP, MODBUS UDP and MODBUS RTU, which can
be run independently of one another simultaneously
Each mode can be configured
10 supported MODBUS services (Function Codes): FC1 to FC6, FC15,
FC16, FC22, FC23
Data exchange via 1000 registers in each of the local MODBUS process
images
768-byte sector that can be addressed by bits in each local MODBUS
process image
Access to a 104 kB flag sector (total of 53248 registers/words, with 3328
addressable bits)
28 Information and configuration registers
Up to 1000 TCP connections
MODBUS communications monitoring using programmable watchdogs
Configurable response on PLC stop
Configurable response on disruption of MODBUS communication
750-8208 PFC200 CS 2ETH RS CAN DPM
Version 1.1.0, valid from FW Version 02.06.20(09)