DIAGNOSIS OF Ale SYSTEM
CONDITION 11
DEFECTIVE THERMOSTATIC SWITCH
lOW SIDEGAUGE
COMPRESSOR
CYCLES "ON"
34
p.i
CYCLES "OFF"
28
p.i
LOW SIDE
HAND
VALVE
CLOSED
LOW SIDE HOSE
CONNECTED
TO
LOW SIDE SERVICE
CONNECTOR
AMBIENT'
, TEMP. 95° F.
HIGH SIDE NORMAL
HIGH
SIDE HOSE
CONNECTED
TO
HIGH
SIDE SERVICE
CONNECTOR
Complaint
Compressor cycles (cuts in and out) too rapidly.
Condition
1.
Low side pressure
cycle
too
high
with
insufficient range between OFF and ON. Cycle
should be:
Cycle "Off"
- 12-15 psi.
Cycle "On" - 36-39 psi.
Cycle Range - 24-28 psi.
2.
High side gauge reading Normal (200 psi).
Should be 185-205 psi at ambient temperature
of 95°F. See chart for
pressures at other
ambient temperatures.
Diagnosis
Thermostatic switch defective.
Correction
1.
Stop engine and turn air conditioner
OFF.
2.
Remove and discard old thermostatic
switch,
install new switch of same type.
3.
When
installing
new
Thermostatic
Switch,
make certain the capillary tube is installed in
same
position
and
to
same
depth
in
evaporator core as old switch tube.
CAUTION
Do not kink or bend capillary tube sharply (tube
is gas filled).
4.
Operate system and check performance
of
new thermostatic switch.
N4-14