Event name
Overvoltage
Description
The power supply voltage exceeded the allowable input voltage range.
EtherCAT Master Function Module Source
Source
Error
Level
attributes
Effects
User program
EtherNet/IP NET RUN
Indicators
System
-defined
variables
Assumed cause
The voltage between the positive
and negative terminals in the
control power supply converter
exceeded the specified value.
The voltage was suddenly
increased by the phase advance
capacitor or the uninterruptible
power supply (UPS).
Cause and
The Regeneration Resistor wiring
correction
is broken.
The External Regeneration
Resistor is not suitable.
The Servo Drive failed.
Attached
None
information
Precautions/
"12" is displayed on the Servo Drive front panel and F012 is given as the AlarmCode (4001 hex).
Remarks
G5-series Linear Motors/Servo Drives With Built-in EtherCAT Communications
details
Minor fault
Recovery
Continues.
Operation
–
Variable
None
Input the correct voltage.
Remove the phase-advancing
capacitor or UPS.
Measure the resistance of the
external resistor between the B1
and B2 terminals on the Servo
Drive. If the resistance is infinite,
the wiring is broken. Replace the
external resistor.
Change the Regeneration Resistor
based on the specified
regeneration resistance and the
calculated power (W).
Replace the Servo Drive.
Event code
Slave
Error reset
(after resetting slave
errors)
Power drive circuit is OFF for relevant slave.
EtherNet/IP NET ERR
–
Data type
–
Correction
Appendices
04A9 0000 hex
Detection
Continuously
timing
System
Log category
EtherNet/IP LINK/ACT
–
Name
–
Prevention
Input the correct voltage.
Do not use a phase-advancing
capacitor or UPS.
None
Determine the Regeneration
Resistor based on the specified
regeneration resistance and the
calculated power (W).
None