Channel-Independent Parameters; Table 2 Parameter Table 130 (Operating Mode); Table 3 Parameter Table 131 (Status) - WAGO 750 Product Manual

Table of Contents

Advertisement

750-1632/000-100

4.3.1 Channel-Independent Parameters

Parameter Table 130 (Operating Mode)
Register Name, Type
0
Parameter Table 131 (Status)
Register Name, Type
0
1
2
3
Product manual | Version: 1.1.0
Proportional Valve Module 2-3-4
Bits, Explanation
VALVE_CONF
1 ... 15 (reserved)
UINT
Bits, Explanation
MST_ERROR,
0
UINT
Undervoltage
1
Temperature error
2
Local bus error
3
Controller communi-
cation error
4
Controller version er-
ror
5 ... 15
MST_WARN-
0
ING,
Temperature warning
UINT
1
Overvoltage
2 ... 15
MST_NOTIFI-
0
CATION,
Limit switch status,
UINT
DI 1
1
Limit switch status,
DI 2
2 ... 15
MST_MOD-
0 ... 15
ULE_
Temperature of the I/
TEMP,
O module in °C
INT
Table 2: Parameter Table 130 (Operating Mode)
Value/Range
Description
(Default)
0
One valve
1 (default)
Two valves
Table 3: Parameter Table 131 (Status)
Value/Range
Description
(Default)
0
No field supply undervoltage
1
Field supply undervoltage
0
No overtemperature in the I/O module
1
Overtemperature in the I/O module
0
Connection to local bus
1
No connection to local bus
0
Connection to controller
1
No connection to controller; no communica-
tion
0
Controller version OK
1
Incompatible controller version
0
(Reserved)
0
Module temperature in operating range
1
Module temperature approaching critical
range
0
No field supply overvoltage
1
Field supply overvoltage
0
(Reserved)
0
Limit switch inactive, DI 1
1
Limit switch active, DI 1
0
Limit switch inactive, DI 2
1
Limit switch active, DI 2
0
(Reserved)
0x8000 ...
One LSB corresponds to one degree Cel-
0x7FFF
sius.
(−32768 ...
0x0000 = 0 °C
32767)
Functions
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

753

Table of Contents