750-468 [4 AI DC 0-10 V, Single-Ended]
Process Image
Some fieldbus systems can process input channel status information by means
of a status byte.
This status byte can be displayed using the starting tool WAGO-I/O-CHECK
2. However, the coupler / controller process operation is optional, which
means that accessing or parsing the status information depends on the fieldbus
system.
Attention
The representation of the process data of some fieldbus modules or their
variations in the process image depends on the fieldbus coupler/-controller
used. Please take this information as well as the particular design of the re-
spective control/status bytes from the section "Fieldbus specific design of the
process data" included in the description of the process image of the corre-
sponding coupler/controller.

2.1.1.7.1 Standard Data Format

For the standard module 750-468, the input voltage ranging from 0 V to 10 V
is scaled on the numerical values ranging from 0x0000 to 0x7FF9.
Process values of module 750-468
Input current
0 V - 10 V
<0.00
'0000.0000.0000.0 000'
0.00
'0000.0000.0000.0 000'
1.25
'0001.0000.0000.0 000'
2.50
'0010.0000.0000.0 000'
3.75
'0011.0000.0000.0 000'
5.00
'0100.0000.0000.0 000'
6.25
'0101.0000.0000.0 000'
7.50
'0110.0000.0000.0 000'
8.75
'0111.0000.0000.0 000'
10.00
'0111.1111.1111.1 000'
>10.00
'0111.1111.1111.1 001'
)
*
status bits: X = not used, F = short-circuit, Ü = oversize
Numerical value
binary
)
value
*
X F Ü
Status-
byte
hex.
dec.
hex.
0x0000
0
0x00
0x0000
0
0x00
0x1000
4096
0x00
0x2000
8192
0x00
0x3000
12288
0x00
0x4000
16384
0x00
0x5000
20480
0x00
0x6000
24576
0x00
0x7000
28672
0x00
0x7FF8
32760
0x00
0x7FF9
32761
0x42
WAGO-I/O-SYSTEM 750
I/O Modules