84
Process Image
7.4
Process Data of the Standard Version 750-464 (RTD,
configurable) Siemens Format
7.4.1

Pt100 (acc. IEC 751)

With the setting "Pt100 (acc. IEC 751)" and activated Siemens format, the I/O
module converts the resistance measured values of Pt100 sensors (acc. IEC 751)
and outputs them as temperature values. The temperature values are displayed at a
resolution of 1 digit per 0.5 °C).
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.

Table 70: Process image for 750-464, Pt100 setting (acc. IEC 751)

Temperature
°C
---
Short circuit
< -200.0
Underrange
-200.0
-100.0
0.0
100.0
200.0
500.0
750.0
800.0
850.0
> 850.0
Overrange
---
Wire break
1) Temperature values below 0 °C are represented in two's complement binary.
2) When short circuit and wire break monitoring is ON (see section "Behavior in the Event of an
Error")
3) When underrange / overrange limit is ON (see section "Behavior in the Event of an Error")
4) Status information: X: Not used, F: Short circuit, wire break, Ü: Overrange
Numeric value
Resistance
Ω
Binary
< 9.00
'1111.0011.1000.0 011'
2)
< 18.52
'1111.0011.1000.0 001'
3)
18.52
'1111.0011.1000.0 000'
60.256
'1111.1001.1100.0 000'
100.000
'0000.0000.0000.0 000'
138.506
'0000.0110.0100.0 000'
175.856
'0000.1100.1000.0 000'
280.978
'0001.1111.0100.0 000'
360.638
'0010.1110.1110.0 000'
375.704
'0011.0010.0000.0 000'
390.481
'0011.0101.0010.0 000'
> 390.481
'0011.0101.0010.0 001'
3)
> 5500.00
'0011.0101.0010.0 011'
2)
WAGO-I/O-SYSTEM 750
750-464 2/4 AI RTD configurable
2)
with status information
XFÜ
Hex.
Dec.
0xF383
-3197
0xF381
-3199
0xF380
-3200
0xF9C0
-1600
0x0000
0x0640
1600
0x0C80
3200
0x1F40
8000
0x2EE0
12000
0x3200
12800
0x3520
13600
0x3521
13601
0x3523
13603
Status
LED
4)
byte
error
hex.
AI 1, 2
0x51
on
0x41
on
0x00
off
0x00
off
0
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x42
on
0x62
on
Manual
Version 1.0.1