250 Appendix
15.3.5.2

SSI Transmitter Interface I/O Modules

The process image depends on the parameterized operating mode!
The operating mode of the configurable I/O module can be set. Based on the
operating mode, the process image of these I/O modules is then the same as
that of the respective version.
In the input process image, SSI transmitter interface modules with status occupy
4 data bytes. Two words are assigned in the process image via word alignment.

Table 162: SSI transmitter interface modules with alternative data format

Input process image
Offset
0
1
15.3.5.3

Distance and Angle Measurement

The incremental encoder interface module occupies 6 bytes of user data in the
input and output area of the process image, 4 data bytes and two additional
control/status bytes. Four words are assigned in the process image via word
alignment.

Table 163: Incremental Encoder Interface

Input and Output Process Image
Offset
0
1
2
3
15.3.5.4

Counter Modules

Operating modes:
"Up/Down Counter / 100 kHz",
"Up Counter / Enable Input",
"Peak Time Counter"
"Frequency Counter"
"Up/Down Counter / Signal Outputs (DO)"
The above Counter Modules have a total of 5 bytes of user data in both the Input
and Output Process Image (4 bytes of counter data and 1 byte of control/status).
The counter value is supplied as 32 bits. The following tables illustrate the Input
Manual
Version 1.7.0, valid from FW Version 04.01.10(23)
Byte designation
High byte
D1
D3
Byte designation
High byte
-
D1
-
D3
WAGO I/O System 750
750-8210/040-000 PFC200; G2; 4ETH; XTR
Low byte
D0
D2
Low byte
C0/S0
Control/status byte of channel 1
D0
C1/S1
Control/status byte of channel 2
D2
Remark
Data bytes
Remark
Data values of channel 1
Data values of channel 2