240
I/O Modules
18.2.5.4

Serial Interface Modules with Standard Data Format

750-650/000-001, -014, -015, -016
750-653/000-001, -006
The above Serial Interface Modules with Standard Data Format have a total of 6
bytes of user data in both the Input and Output Process Image (5 bytes of serial
data and 1 byte of control/status). The following table illustrates the Input and
Output Process Image, which have a total of 3 words mapped into each image.
Word alignment is applied.

Table 108: Serial Interface Modules with Standard Data Format

Input and Output Process Image
Offset
0
1
2
18.2.5.5

Data Exchange Module

750-654, (and the variation /000-001)
The Data Exchange modules have a total of 4 bytes of user data in both the Input
and Output Process Image. The following tables illustrate the Input and Output
Process Image, which has a total of 2 words mapped into each image.
Word alignment is applied.

Table 109: Data Exchange Module

Input and Output Process Image
Offset
0
1
18.2.5.6

SSI Transmitter Interface Modules

750-630 (and all variations)
The process image of the / 003-000-variants depends on the parameterized
operating mode!
The operating mode of the configurable /003-000 I/O module versions can be set.
Based on the operating mode, the process image of these I/O modules is then the
same as that of the respective version.
Byte Destination
High Byte
D0
D2
D4
Byte Destination
High Byte
D1
D3
WAGO-I/O-SYSTEM 750
758-874/000-131 WAGO-I/O-IPC-C6
Low Byte
C/S
Data byte
D1
D3
Low Byte
D0
D2
Description
Control/status
byte
Data bytes
Description
Data bytes