Standard Data Format - WAGO -I/O-SYSTEM750 Manual

Fieldbus independent i/o modules 4 ai 4-20 ma, single-ended
Table of Contents

Advertisement

2.1.1.7.1

Standard Data Format

For the standard module 750-455 , the input current ranging from 4 mA to
20 mA is scaled on the numerical values ranging from 0x0000 to 0x7FFF.
WAGO-I/O-SYSTEM 750
I/O Modules
Input current
4 mA - 20 mA
Measured value
<4.0
'0000.0000.0000.0 X11'
4.0
'0000.0000.0000.0 X00'
5.6
'0000.1100.1100.1 X00'
7.2
'0001.1001.1001.1 X00'
8.8
'0010.0110.0110.0 X00'
10.4
'0011.0011.0011.0 X00'
12.0
'0100.0000.0000.0 X00'
13.6
'0100.1100.1100.1 X00'
15.2
'0101.1001.1001.1 X00'
16.8
'0110.0110.0110.0 X00'
18.4
'0111.0011.0011.0 X00'
20.0
'0111.1111.1111.1 X00'
>20.0
'0111.1111.1111.1 X11'
)
*
status bits: X = not used, F = short-circuit, Ü = oversize
750-455(/xxx-xxx) [4 AI 4-20 mA, Single-Ended]
Process values of module 750-455
numerical value
binary
)
*
X F Ü
Process Image
Status-
byte
hex.
dec.
hex.
0x0003
0
0x41
0x0000
0
0x00
0x0CCC
3276
0x00
0x1998
6552
0x00
0x2664
9828
0x00
0x3330
13104
0x00
0x4000
16384
0x00
0x4CCC 19660
0x00
0x5998
22936
0x00
0x6660
26208
0x00
0x7330
29488
0x00
0x7FFC 32764
0x00
0x7FFF
32767
0x42
• 13
LED
Error
AI 1...4
on
off
off
off
off
off
off
off
off
off
off
off
on

Advertisement