Standard Data Format - WAGO 750-462 Series Manual

Fieldbus independent i/o modules, 2 ai thermocouple
Table of Contents

Advertisement

2.1.1.7.1.1 Standard Data Format

For the 750-462 module and its variations with standard data format, the
temperature values of the sensors are represented with a resolution of 1 digit
per 0.1 °C within a word (16 bits). Thus, 0 °C corresponds to the numeric
value 0x0000 and 100 °C to 0x03E8 (dec. 1000).
Temperature
>ca.1370.0
1)
WAGO-I/O-SYSTEM 750
I/O Modules
°C
<-100.0
'1111.1100.0001.1000'
-100.0
'1111.1100.0001.1000'
0.0
'0000.0000.0000.0000'
100.0
'0000.0011.1110.1000'
200.0
'0000.0111.1101.0000'
300.0
'0000.1011.1011.1000'
400.0
'0000.1111.1010.0000'
500.0
'0001.0011.1000.1000'
1000.0
'0010.0111.0001.0000'
1200.0
'0010.1110.1110.0000'
1300.0
'0011.0010.1100.1000'
1370.0
'0011.0101.1000.0100'
'0011.0101.1000.0100'
Temperature values below 0 °C are represented in two's complement binary form.
750-462 (/xxx-xxx) [2 AI Thermocouple] • 13
750-462, Type K
1)
Numerical value
binary
hex.
0xFC18
0xFC18
0x0000
0x03E8
0x07D0
0x0BB8
0x0FA0
0x1388
0x2710
0x2EE0
0x32C8
0x3584
>0x3584
Process Image
Status-
LED
byte
Error
dec.
hex.
AI 1, 2
-1000
0x41
on
-1000
0x00
off
0
0x00
off
1000
0x00
off
2000
0x00
off
3000
0x00
off
4000
0x00
off
5000
0x00
off
10000
0x00
off
12000
0x00
off
13000
0x00
off
13700
0x00
off
>13700
0x42
on

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents