Sensors For Temperature Measurement (°C); Standard Data Format; Table 24: Process Image Type E, Id0, Two's Complement Representation - WAGO 750 Series Manual

I/o system 8ai; tc; adjust 8-channel analog input; thermocouple; adjustable
Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

36
Process Image
4.3.2
Sensors for Temperature Measurement (°C)
4.3.2.1

Standard Data Format

For I/O module 750-498, the temperature values of the sensors are displayed at
a resolution of 1 digit per 0.1 °C in one word (16-bit). As a result, 0 °C
corresponds to the numeric value 0x0000 and 100 °C to the numeric value
0x03E8 (dec. 1000). The temperature underranges and overranges refer to
manufacturer range violations.

Table 24: Process Image Type E, ID0, Two's Complement Representation

Temperature
°C
---
Range violation, cold
junction
< −200.0
Underrange
−200.0
−100.0
0.0
100.0
200.0
300.0
400.0
500.0
600.0
700.0
900.0
999.0
1000.0
Overrange
> 1000.0
Wire break
---
1)
Temperature values below 0 °C are represented in two's complement binary.
Manual
Version 1.0.0
Numeric value
Binary
'1000.0000.0000.0000'
'1111.1000.0011.0000'
'1111.1000.0011.0000'
'1111.1100.0001.1000'
'0000.0000.0000.0000'
'0000.0011.1110.1000'
'0000.0111.1101.0000'
'0000.1011.1011.1000'
'0000.1111.1010.0000'
'0001.0011.1000.1000'
'0001.0111.0111.0000'
'0001.1011.0101.1000'
'0010.0011.0010.1000'
'0010.0111.0000.0110'
'0010.0111.0001.0000'
'0010.0111.0001.0000'
'0111.1111.1111.1111'
WAGO I/O SYSTEM 750
750-498 8AI; TC; Adjust
1)
Hex.
Dec.
0x8000
−32768
0xF830
−2000
0xF830
−2000
0xFC18
−1000
0x0000
0
0x03E8
1000
0x07D0
2000
0x0BB8
3000
0x0FA0
4000
0x1388
5000
0x1770
6000
0x1B58
7000
0x2328
9000
0x2706
9990
0x2710
10000
0x2710
10000
0x7FFF
32767
Status
Error
Byte
LED
Hex.
0x00
OFF
0x41
ON
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x42
ON
0x60
ON