Standard Data Format - WAGO I/O-SYSTEM 750-478 Manual

Fieldbus independent i/o modules 2 ai dc 0-10 v, single-ended
Table of Contents

Advertisement

12 •
750-478 [2 AI DC 0-10 V, Single-Ended]
Process Image
2.1.1.6.1

Standard Data Format

For the standard module 750-478, the input voltage ranging from 0 V to 10 V
is scaled on the numerical values ranging from 0x0000 to 0x7FFF.
Input voltage
0 V - 10 V
Measured value
<-1.00
'0000.0000.0000.0000'
<-0.50
'0000.0000.0000.0000'
0.00
'0000.0000.0000.0000'
1.25
'0001.0000.0000.0000'
2.50
'0010.0000.0000.0000'
3.75
'0011.0000.0000.0000'
5.00
'0100.0000.0000.0000'
6.25
'0101.0000.0000.0000'
7.50
'0110.0000.0000.0000'
8.75
'0111.0000.0000.0000'
10.00
'0111.1111.1111.1111'
>10.50
'0111.1111.1111.1111'
>11.00
'0111.1111.1111.1111'
Process values of module 750-478
numerical value
binary
hex.
0x0000
0x0000
0x0000
0x1000
0x2000
0x3000
0x4000
0x5000
0x6000
0x7000
0x7FFF
0x7FFF
0x7FFF
Status-
LED
byte
Error
dec.
Hex.
AI 1, 2
0
0x41
on
0
0x41
off
0
0x00
off
4096
0x00
off
8192
0x00
off
12288
0x00
off
16384
0x00
off
20480
0x00
off
24576
0x00
off
28672
0x00
off
32767
0x00
off
32767
0x42
off
32767
0x42
on