112 Commissioning
Select the "Network" tab:
6.
Figure 43: "WAGO Ethernet Settings" – "Network" Tab
To assign a fixed address, select "Static configuration" on the "Source" line
7.
under "Input". DHCP is normally activated as the default setting.
In the column "Input" enter the required IP address and, if applicable, the
8.
address of the subnet mask and of the gateway.
9.
Click on [Write] to accept the address in the controller. (If necessary,
"WAGO Ethernet Settings" will restart your controller. This action may
require about 30 seconds.)
You can now close "WAGO Ethernet Settings", or make other changes
10.
directly in the Web-based Management system as required. To do this,
click on [Run WBM] at the right in the window.
Manual
Version 1.7.0, valid from FW Version 04.01.10(23)
WAGO I/O System 750
750-8210/040-000 PFC200; G2; 4ETH; XTR