Functions; Process Image; Table 19: Input Process Data - Connections 1 To 4 - WAGO TEchDocs 765-4501/0100-0000 Manual

8-port io-link master class a; ethernet/ip; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

765-4501/0100-0000

Functions

5

5.1 Process Image

This section describes the process data. The structure of the process data depends on
which connection (connection 1, connection 2 etc.) is used between the EtherNet/IP
scanner and the module. The module offers multiple connections; a connection was se-
lected during configuration of the EtherNet/IP scanner.
List of Connections
• Connection 1: Exclusive Owner – 32 bytes per IO-Link port
• Connection 2: Exclusive Owner – 32 bytes per IO-Link port without config
• Connection 3: Listen Only – 32 bytes per IO-Link port
• Connection 4: Input Only – 32 bytes per IO-Link port
• Connection 5: Exclusive Owner – 16 bytes per IO-Link port
• Connection 6: Exclusive Owner – 16 bytes per IO-Link port without config
• Connection 7: Listen Only – 16 bytes per IO-Link port
• Connection 8: Input Only – 16 bytes per IO-Link port
• Connection 9: Exclusive Owner – 4 bytes per IO-Link port
• Connection 10: Exclusive Owner – 4 bytes per IO-Link port without config
• Connection 11: Listen Only – 4 bytes per IO-Link port
• Connection 12: Input Only – 4 bytes per IO-Link port
The following sections describe the process image for each connection.
Input Process Data of Connections 1 to 4
The following table describes the structure of the input process data of connections 1
through 4.
Byte Off-
set
1
2
3 ... 4
5
6
7 ... 38
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
Byte
Input Process Data
Count
1
DI status
1
Dummy byte
2
DI data
1
Port X01: IO-Link PQI
1
Dummy byte
32
Port X01 (pin 4) functions as IO-
Link master: IO-Link input data
Port X01 (pin 4) functions as a
digital input: input data
Port X01 (pin 4) functions as
digital output: output data
Table 19: Input Process Data – Connections 1 to 4
Description
0: DI data invalid.
1–255: DI data valid.
Reserved, 0
The port and pin assignment of process data depends
on the process data layout setting: pin-based or port-
based. See the following tables.
8 Process Image
See
[} 47].
Reserved, 0
IO-Link input data of the IO-Link device on port X01.
For a description of the data, see the manual from the
manufacture of the IO-Link device used.
Byte 7:
Bit 0 = 0: input off. Bit 0 = 1: Input on.
Bits 1 ... 7: always 0.
Byte 8 ... 38: reserved.
Byte 7:
Bit 0 = 0: output off. Bit 0 = 1: Input on.
Bits 1 ... 7: always 0.