Channel-Dependent Parameters; Table 7 Parameter Table 150 (Process Data Handling, Valve 1) - WAGO 750 Product Manual

Table of Contents

Advertisement

Functions

4.3.2 Channel-Dependent Parameters

Parameter Tables 150 and 151 (Process Data Handling, Valve 1, Valve 2)
Tables 150 and 151 have identical structures. As an example, Table 150 is explained
here for valve 1.
Register Name, Type
0
1
2
3
4
5
6
7
34
Product manual | Version: 1.1.0
Proportional Valve Module 2-3-4
Bits, Explana-
tion
PH_SUBST_
0 ... 15
STRA,
Substitute
UINT
value strategy
PH_SUBST_
0 ... 15
CURR,
Substitute
INT
value for the
output current
PH_TIP_
0 ... 15
MODE,
JOG mode
UINT
PH_TIP_
0 ... 15
TIME,
Time period
UINT
PH_TARGET_
0 ... 15
WINDOW,
Window for
UINT
ON_TARGET
status bit in
0.01 % around
setpoint
PH_COIL_
0 ... 15
CURRENT_
Selection of the
DISPLAY,
value to be
UINT
shown in the
PLC input data
EndStopFunc-
0  ... 15
tion,
End stop be-
UINT
havior
EndStopCur-
0  ... 15
rent,
End stop value
INT
to be ap-
proached
Table 7: Parameter Table 150 (Process Data Handling, Valve 1)
Value/Range
Description
(Default)
0 (default)
Output the last value from the process image.
1
Output the value according to
PH_SUBST_CURR.
−10000 ...
One LSB corresponds to 0.01 % of the maximum
+10000
current.
(Default: 0)
0 (default)
JOG mode if activated in V1_CTRL
1
TIPP mode if activated in V1_CTRL
0 ... 32767
In TIP mode, the current changes according to
(Default: 100)
the ramp setting, but at most for the amount of
time specified in PH_TIP_TIME [given in ms].
0 ... 2000
ON_TARGET is set if the internal output value is
(Default: 200)
within the window around the setpoint.
0 (default)
Current in mA with filter
Actual current in 0.1 mA (10000 corresponds to
1.0 A).
The measured value filter is active.
1
Current in % with filter
Actual current in 0.01 % of nominal current
(10000 corresponds to 100.00 %).
The measured value filter is active.
2
Current in mA without filter
Actual current in 0.1 mA (10000 corresponds to
1.0 A).
The measured value filter is not active.
3
Current in % without filter
Actual current in 0.01 % of nominal current
(10000 corresponds to 100.00 %).
The measured value filter is inactive.
0 (default)
Hold present actual value.
1
Approach end stop value with stop ramp.
2
Approach end stop value with ramp 1.
3
Approach end stop value with ramp 2.
4
Approach end stop value with ramp 3.
5
Approach end stop value with ramp 4.
−10000 ...
One LSB corresponds to 0.01 % of the permitted
+10000
maximum current.
(Default: 0)
750-1632/000-100