3.5.2 IEC 61131-3 Program Transfer

Program transfer from the PC to the controller following programming of the
desired IEC 61131 application can be made in two different ways:
• via the serial interface or
• via the field bus.
A suitable communication driver each is required for both types.
More Information
For information on the installation of the communication drivers as well as
details regarding the use of the software, please refer to the
WAGO-I/O-PRO manual .
Note
The station address 0 starts up the controller after switching on POWER-ON
and it also starts the PFC functions without the field bus being active.
This function allows an autarkic smallest scale control with the
WAGO-I/O-SYSTEM 750.
Autarkic smallest scale control
Any station address may be used from SW 03. The user determines whether
the controller may start up with the default configuration using a functional
building block.
3.5.2.1

Transmission via the Serial Interface

Use the WAGO communication cable to produce a physical connection via the
serial interface. This is contained in the scope of delivery of the programming
tool IEC 1131-3, order No.: 759-333, or can be purchased as an accessory
under order No.: 750-920.
Connect the COM port of your PC with the communication interface of your
controller via the WAGO communication cable.
Warning
The communication cable 750-920 must not be connected or disconnected
while the coupler/controller is powered on!
A communication driver is required for serial data transmission. In
WAGO-I/O-PRO , this driver and its parameters are entered in the
"Communication parameters" dialog.
WAGO-I/O-SYSTEM 750
Bus System
Programmable Field Bus Controller 750-833
Programming of the PFC with WAGO-I/O-PRO
• 71