Adjustment Level (L.adj) - Omron E5AR-T User Manual

Programmable digital controller
Hide thumbs Also See for E5AR-T:
Table of Contents

Advertisement

CH
AT Execute/Cancel
Function
Operation
Reference
Reference
Communications Writing
Function
Operation
Reference
Reference
at
This parameter is used to execute auto-tuning (AT).
• When auto-tuning is executed, the MV is increased and decreased
around the SP to obtain the characteristics of the object of control.
The PID constants are calculated from the results and the Propor-
tional Band, Integral Time, and Derivative Time parameters are
automatically set.
• Normally this parameter is off. AT is executed by pressing the U
Key to select the PID set number. AT cannot be executed while
control is stopped.
• Select 0 to specify the PID set currently being used for control.
Select a number from 1 to 8 to specify a PID set number.
• The AT Execute/Cancel parameter automatically returns to off
when finished.
• The SP flashes if the Present Value (PV)/Preset Set Point parameter
is monitored during AT.
• The channel cannot be changed during AT.
● Related Information
4.10 Determining the PID Constants (AT or Manual Settings) (P. 4-
33)
● Related Parameters
PID
Proportional Band, PID
Time (PID Setting Level) (P. 8-40)
cmwt
• This parameter enables or disables the writing of set values from a
host (computer) to the Controller.
• The default setting is off (Disabled).
Select on to enable or off to disable writing set values via communi-
cations.
● Related Parameters
Communications Protocol Selection (Communications Setting Level)
(P. 8-85)
Communications Unit No (Communications Setting Level) (P. 8-85)
Communications Speed (Communications Setting Level) (P. 8-85)
Communications Data Length (Communications Setting Level) (P. 8-
86)
Communications Stop Bit (Communications Setting Level) (P. 8-86)
Communications Parity (Communications Setting Level) (P. 8-86)
Transmission Wait Time (Communications Setting Level) (P. 8-87)

8.5 Adjustment Level (l.adj)

Auto Mode, running
Integral Time, and PID
Models that support communications
l.adj
Derivative
l.adj
8-23