CH
PV Dead Band
Function
Setting
Reference
Reference
Input
Cold Junction Compensation
: 1 to 4)
Function
Setting
Reference
Reference
8.18 Expansion Control Setting Level (l.exc)
p-db
• This parameter is used on a Position-proportional Control Model so
that PV = SP when the PV is within the PV dead band.
• This function prevents unnecessary output when the PV is near the
SP.
Setting range
0 to 99999
● Related Parameters
Closed/Floating (Control Initial Setting Level) (P. 8-59)
Motor Calibration (Control Initial Setting 2 Level) (P. 8-72)
Travel Time (Control Initial Setting 2 Level) (P. 8-73)
Position-proportional Dead Band (Adjustment Level) (P. 8-27)
Open/Close Hysteresis (Adjustment Level) (P. 8-28)
Operation at Potentiometer Input Error (Expansion Control Setting
Level) (P. 8-104)
cjc.*
• When using a thermocouple input, these parameters are used to
specify whether cold junction compensation is performed inside the
Controller or outside the Controller.
• Select "External" when two thermocouples are used to measure the
temperature difference or when an external cold junction compen-
sator is used for increased accuracy.
Setting range
off:
External
on:
Internal
● Related Parameters
Input
Type (Input Initial Setting Level) (P. 8-50)
Position-proportional Control Model
Unit
Default value
EU
0
Thermocouple input
Unit
Default value
on: Internal
l.exc
l.exc
8-99