CH
SP Upper Limit
SP Lower Limit
Function
Setting
Reference
Reference
sl-h
sl-l
• Use these parameters to set upper and lower limits for the SP
setting. The SP can be set only between these limits. If the limits are
changed and a previously set SP falls outside of the limits due to the
change, the SP will automatically change to the upper or lower limit.
• If the input type and temperature unit are changed, the SP upper
and lower limits will change to the upper and lower limits of the
sensor.
• The decimal point position depends on the selected sensor. For
analog input, the decimal point position is determined by the
Decimal Point Position parameter.
Parameter
Setting range
Temperature: SP lower limit + 1
to upper limit of input range
SP Upper
Analog: (SP lower limit + 1) to
Limit
(smaller of 99999 and display
value equivalent to input upper
limit)
Temperature: Lower limit of
input range to SP upper limit 1
SP Lower
Limit
Analog: (Larger of -19999 and
display value equivalent to input
lower limit) to SP upper limit
● Related Parameters
Input
Type (Input Initial Setting Level) (P. 8-50)
Input
Temperature Units (Input Initial Setting Level) (P. 8-51)
8.12 Control Initial Setting Level (l.1)
Unit
Default value
EU
1300.0
EU
200.0
1
l.1
8-57