Section 8 Parameters
Output 1 Type
Output 3 Type
Function
Setting
Reference
Reference
Linear Current Output
( : 1 to 4)
Function
Setting
Reference
Reference
8-56
o1-t
o3-t
Use these parameters to select the output types for multi-outputs.
• Select a pulse voltage output or linear current output.
• When pulse voltage output is selected, the output is 12 VDC, 21 mA
for the E5AR-TQQ@@WW-@@@ and 12 VDC, 40 mA for all other
models.
• When linear current output is selected, use the Linear Current
Output Type parameter to select an output of 0 to 20 mA or 4 to
20 mA.
Setting range
0: Pulse voltage output
1: Linear current output
● Related Parameters
Linear Current Output
Control/Transfer Output
Level) (P. 8-64)
co*-t
Type
Use these parameters to select the linear current output types.
• Select a 0 to 20 mA output or a 4 to 20 mA output.
Setting range
0: 0 to 20 mA
1: 4 to 20 mA
● Related Parameters
Control/Transfer Output
Level) (P. 8-64)
Model with multi-output
Unit
Type (Control Initial Setting Level) (P. 8-56)
Assignment (Control Initial Setting 2
Unit
Assignment (Control Initial Setting 2
l.1
Default value
0
l.1
Current output
Default value
1